meta: yosemite4: Adjust fan duty for corner case
Modified the fan table for the following corner cases, based on the
thermal team's requirements:
1. When one fan fails, fan duty is set to 90%.
2. When one slot is unplugged during service time, fan duty
is set to 90%.
Change-Id: Ia378e5917ef1dbe41b8c832e235ffd1914d401a7
Signed-off-by: Eric Yang <eric.yang.wiwynn@gmail.com>
diff --git a/configurations/meta/yosemite4.json b/configurations/meta/yosemite4.json
index bede302..3bc1c9e 100644
--- a/configurations/meta/yosemite4.json
+++ b/configurations/meta/yosemite4.json
@@ -494,7 +494,7 @@
"Class": "fan",
"FFGainCoefficient": 1.0,
"FFOffCoefficient": 0.0,
- "FailSafePercent": 80.0,
+ "FailSafePercent": 90.0,
"ICoefficient": 0.0,
"ILimitMax": 0.0,
"ILimitMin": 0.0,
@@ -665,7 +665,7 @@
100.0,
100.0,
100.0,
- 80.0,
+ 90.0,
10.0
],
"PositiveHysteresis": 0,
diff --git a/configurations/meta/yosemite4n.json b/configurations/meta/yosemite4n.json
index 3da9387..39c6ee7 100644
--- a/configurations/meta/yosemite4n.json
+++ b/configurations/meta/yosemite4n.json
@@ -462,7 +462,7 @@
"Class": "fan",
"FFGainCoefficient": 1.0,
"FFOffCoefficient": 0.0,
- "FailSafePercent": 80.0,
+ "FailSafePercent": 90.0,
"ICoefficient": 0.0,
"ILimitMax": 0.0,
"ILimitMin": 0.0,
@@ -633,7 +633,7 @@
100.0,
100.0,
100.0,
- 80.0,
+ 90.0,
10.0
],
"PositiveHysteresis": 0,