monitor : do not trigger error when inventory unavailable
Under some startup scenarios, fan-monitor can start before the
InventoryManager service has populated inventory. This leads to
false-positives when marking fans non-functional.
This fix detects D-Bus exceptions and defaults the fans to functional.
They subscribe to the interfaces-added signal which will populate the
fans with correct values as soon as Inventory Manager completes startup.
Signed-off-by: Mike Capps <mikepcapps@gmail.com>
Change-Id: I14bff20da14cba3f5ef4b79763867b5cecab0267