pid/zone: Restore PWM when fans returned to auto This makes use of the improved write() interface, to allow the PID-loop-determined PWM to be restored, when the fan is returned to automatic mode. Without this fix, a fan set to manual mode, then manually set to a different speed, would not properly return to the correct speed, when transitioning back to automatic from manual. This patch also adds a stub to allow the caller to learn the raw PWM value written as output, another useful write() interface improvement. Although not the topic of this change, it is included here, to avoid later patch conflicts. Tested: I can now correctly toggle between automatic, and manual, fan control. Upon resuming automatic control, after a few seconds, the fan PWM is now properly restored, to what the PID loop wanted it to be at. Signed-off-by: Josh Lehan <krellan@google.com> Signed-off-by: Jason Ling <jasonling@google.com> Change-Id: I46fc65d6b931755d51093ea475c64cf5e3e6bacb
This is a daemon running within the OpenBMC environment. It uses a well-defined configuration file to control the temperature of the tray components to keep them within operating conditions. It may require coordination with host-side tooling and OpenBMC.
The BMC will run a daemon that controls the fans by pre-defined zones. The application will use thermal control, such that each defined zone is kept within a range and adjusted based on thermal information provided from locally readable sensors as well as host-provided information over an IPMI OEM command.
A system (or tray) will be broken out into one or more zones, specified via configuration files or dbus. Each zone will contain at least one fan and at least one temperature sensor and some device margins. The sensor data can be provided via sysfs, dbus, or through IPMI. In either case, default margins should be provided in case of failure or other unknown situation.
The system will run a control loop for each zone with the attempt to maintain the temperature within that zone within the margin for the devices specified.
How to configure phosphor-pid-control
The software will run as a multi-threaded daemon that runs a control loop for each zone, and has a master thread which listens for dbus messages. Each zone will require at least one fan that it exclusively controls, however, zones can share temperature sensors.
In this figure the communications channels between swampd and ipmid and phosphor-hwmon are laid out.
A configuration file will need to exist for each board.
Each zone must have at least one fan that it exclusively controls. Each zone must have at least one temperature sensor, but they may be shared.
The internal thermometers specified can be read via sysfs or dbus.
Due to data center requirements, the delta between the outgoing air temperature and the environmental air temperature must be no greater than 15C.
Tools needs to update the thermal controller with information not necessarily available to the BMC. This will comprise of a list of temperature (or margin?) sensors that are updated by the set sensor command. Because they don't represent real sensors in the system, the set sensor handler can simply broadcast the update as a properties update on dbus when it receives the command over IPMI.
A tool can override a specific fan's PWM when we implement the set sensor IPMI command pathway.
A tool can read fan_tach through the normal IPMI interface presently exported for sensors.
The plan is to listen for fan_tach updates for each fan in a background thread. This will receive an update from phosphor-hwmon each time it updates any sensor it cares about.
By default phosphor-hwmon reads each sensor in turn and then sleeps for 1 second. We'll be updating phosphor-hwmon to sleep for a shorter period -- how short though is still TBD. We'll also be updating phosphor-hwmon to support pwm as a target.
Each zone will require a control loop that monitors the associated thermals and controls the fan(s). The EC PID loop is designed to hit the fans 10 times per second to drive them to the desired value and read the sensors once per second. We'll be receiving sensor updates with such regularly, however, at present it takes ~0.13s to read all 8 fans. Which can't be read constantly without bringing the system to its knees -- in that all CPU cycles would be spent reading the fans. TBD on how frequently we'll be reading the fan sensors and the impact this will have.
The main thread will manage the other threads, and process the initial configuration files. It will also register a dbus handler for the OEM message.
By default, swampd won't log information. To enable logging pass "-l" on the command line with a parameter that is the folder into which to write the logs.
The log files will be named {folderpath}/zone_{zoneid}.log
.
To enable tuning, pass "-t" on the command line.
See Logging & Tuning for more information.
The code is broken out into modules as follows:
dbus
- Any read or write interface that uses dbus primarily.experiments
- Small execution paths that allow for fan examination including how quickly fans respond to changes.ipmi
- Manual control for any zone is handled by receiving an IPMI message. This holds the ipmid provider for receiving those messages and sending them onto swampd.notimpl
- These are read-only and write-only interface implementations that can be dropped into a pluggable sensor to make it complete.pid
- This contains all the PID associated code, including the zone definition, controller definition, and the PID computational code.scripts
- This contains the scripts that convert YAML into C++.sensors
- This contains a couple of sensor types including the pluggable sensor's definition. It also holds the sensor manager.sysfs
- This contains code that reads from or writes to sysfs.threads
- Most of swampd's threads run in this method where there's just a dbus bus that we manage.A single zone system where multiple margin thermal sensors are fed into one PID that generates the output RPM for a set of fans controlled by one PID. margin sensors as input to thermal pid fleeting0+---->+-------+ +-------+ Thermal PID sampled | min()+--->+ PID | slower rate. fleeting1+---->+-------+ +---+---+ | | | RPM setpoint Current RPM v +--+-----+ The Fan PID fan0+---> | New PWM +-->fan0 samples at a | | | faster rate fan1+---> PID +---------->--->fan1 speeding up the | | | fans. fan2+---> | +-->fan2 ^ +--------+ + | | +-------------------------------+ RPM updated by PWM.