rename away from RPM
The SetPoint output from a thermal PID is likely RPM, and that value is
then fed into a fan controller PID as the set-point (unit: RPM). This
does not have to be RPM, however. Continue renaming variables and
methods to remove the explicit unit-naming.
Signed-off-by: Patrick Venture <venture@google.com>
Change-Id: I570dee0c688338f9a458cac7123314717bee2b42
diff --git a/conf.hpp b/conf.hpp
index 35c2da5..95bdeaa 100644
--- a/conf.hpp
+++ b/conf.hpp
@@ -48,7 +48,7 @@
*/
struct ZoneConfig
{
- /* The minimum RPM value we would ever want. */
+ /* The minimum set-point value we would ever want (typically in RPM) */
double minThermalOutput;
/* If the sensors are in fail-safe mode, this is the percentage to use. */