commit | 2916ea52b3d4c9ba0d0d90c1e33f333aeb720047 | [log] [tgz] |
---|---|---|
author | Brandon Wyman <bjwyman@gmail.com> | Sat Nov 06 03:31:18 2021 +0000 |
committer | Shawn McCarney <shawnmm@us.ibm.com> | Mon Nov 15 16:32:23 2021 +0000 |
tree | b01286a448b77c4bc86c36d1ea075b1c62b51a59 | |
parent | 96893a469bb867b45489fc8b3c1ca34ed9ae1c57 [diff] |
psu-ng: Add in detection of PGOOD fault If STATUS_WORD has bit 11 high (POWER_GOOD# is inactive) or bit 6 high (unit is OFF), consider that a PGOOD fault. Lowest priority error to check, log an error if a power supply has a PGOOD fault, call out the power supply. Tested: Simulated POWER_GOOD# / OFF and verified error logged. Verified normal operations on real hardware do not log error. Get power supply in bad state via i2cset commands: 1. Write 0x19 to 0x02 (ON_OFF_CONFIG, OPERATION command only). 2. Write 0x00 to 0x01 (Immediate off OPERATION command). 3. Restart service, error logged for STATUS_WORD = 0x0800. 4. Write 0x19 to 0x02, 0x00 to 0x01 while powered on. 5. Error logged for STATUS_WORD=0x0840. Change-Id: I24dd1db780510d39dc245e76977099f790a2e59e Signed-off-by: Brandon Wyman <bjwyman@gmail.com>
This repository contains applications for configuring and monitoring devices that deliver power to the system.
To build all applications in this repository:
meson build ninja -C build
To clean the repository and remove all build output:
rm -rf build
You can specify meson options to customize the build process. For example, you can specify:
Several applications in this repository require a PSU JSON config to run. The JSON config file provides information for:
There is an example psu.json to describe the necessary configurations.
inventoryPMBusAccessType
defines the pmbus access type, which tells the service which sysfs type to use to read the attributes. The possible values are:/sys/bus/i2c/devices/3-0069/
/sys/bus/i2c/devices/3-0069/hwmon/hwmonX/
/sys/kernel/debug/pmbus/hwmonX/
/sys/kernel/debug/pmbus/hwmonX/cffps1/
fruConfigs
defines the mapping between the attribute file and the FRU inventory interface and property. The configuration example below indicates that the service will read part_number
attribute file from a directory specified by the above pmbus access type, and assign to PartNumber
property in xyz.openbmc_project.Inventory.Decorator.Asset
interface."fruConfigs": [ { "propertyName": "PartNumber", "fileName": "part_number", "interface": "xyz.openbmc_project.Inventory.Decorator.Asset" } ]
psuDevices
defines the kernel device dir for each PSU in inventory. The configuration example below indicates that powersupply0
's device is located in /sys/bus/i2c/devices/3-0069
."psuDevices": { "/xyz/openbmc_project/inventory/system/chassis/motherboard/powersupply0" : "/sys/bus/i2c/devices/3-0069", }