| <?xml version="1.0" encoding="UTF-8"?> |
| <!----> |
| <!--################################################################################ --> |
| <!--# Redfish Schema: Circuit v1.0.1 --> |
| <!--# --> |
| <!--# For a detailed change log, see the README file contained in the DSP8010 bundle, --> |
| <!--# available at http://www.dmtf.org/standards/redfish --> |
| <!--# Copyright 2018-2020 DMTF. --> |
| <!--# For the full DMTF copyright policy, see http://www.dmtf.org/about/policies/copyright --> |
| <!--################################################################################ --> |
| <!----> |
| <edmx:Edmx xmlns:edmx="http://docs.oasis-open.org/odata/ns/edmx" Version="4.0"> |
| |
| <edmx:Reference Uri="http://docs.oasis-open.org/odata/odata/v4.0/errata03/csd01/complete/vocabularies/Org.OData.Core.V1.xml"> |
| <edmx:Include Namespace="Org.OData.Core.V1" Alias="OData"/> |
| </edmx:Reference> |
| <edmx:Reference Uri="http://docs.oasis-open.org/odata/odata/v4.0/errata03/csd01/complete/vocabularies/Org.OData.Capabilities.V1.xml"> |
| <edmx:Include Namespace="Org.OData.Capabilities.V1" Alias="Capabilities"/> |
| </edmx:Reference> |
| <edmx:Reference Uri="http://docs.oasis-open.org/odata/odata/v4.0/errata03/csd01/complete/vocabularies/Org.OData.Measures.V1.xml"> |
| <edmx:Include Namespace="Org.OData.Measures.V1" Alias="Measures"/> |
| </edmx:Reference> |
| <edmx:Reference Uri="http://redfish.dmtf.org/schemas/v1/RedfishExtensions_v1.xml"> |
| <edmx:Include Namespace="RedfishExtensions.v1_0_0" Alias="Redfish"/> |
| <edmx:Include Namespace="Validation.v1_0_0" Alias="Validation"/> |
| </edmx:Reference> |
| <edmx:Reference Uri="http://redfish.dmtf.org/schemas/v1/Resource_v1.xml"> |
| <edmx:Include Namespace="Resource"/> |
| <edmx:Include Namespace="Resource.v1_0_0"/> |
| </edmx:Reference> |
| <edmx:Reference Uri="http://redfish.dmtf.org/schemas/v1/Sensor_v1.xml"> |
| <edmx:Include Namespace="Sensor"/> |
| </edmx:Reference> |
| <edmx:Reference Uri="http://redfish.dmtf.org/schemas/v1/Outlet_v1.xml"> |
| <edmx:Include Namespace="Outlet"/> |
| </edmx:Reference> |
| |
| <edmx:DataServices> |
| |
| <Schema xmlns="http://docs.oasis-open.org/odata/ns/edm" Namespace="Circuit"> |
| <Annotation Term="Redfish.OwningEntity" String="DMTF"/> |
| |
| <EntityType Name="Circuit" BaseType="Resource.v1_0_0.Resource" Abstract="true"> |
| <Annotation Term="OData.Description" String="This is the schema definition for an electrical circuit."/> |
| <Annotation Term="OData.LongDescription" String="This resource shall be used to represent an electrical circuit for a Redfish implementation."/> |
| <Annotation Term="Capabilities.InsertRestrictions"> |
| <Record> |
| <PropertyValue Property="Insertable" Bool="false"/> |
| </Record> |
| </Annotation> |
| <Annotation Term="Capabilities.UpdateRestrictions"> |
| <Record> |
| <PropertyValue Property="Updatable" Bool="true"/> |
| <Annotation Term="OData.Description" String="Any writable properties can be updated."/> |
| </Record> |
| </Annotation> |
| <Annotation Term="Capabilities.DeleteRestrictions"> |
| <Record> |
| <PropertyValue Property="Deletable" Bool="false"/> |
| </Record> |
| </Annotation> |
| <Annotation Term="Redfish.Uris"> |
| <Collection> |
| <String>/redfish/v1/PowerEquipment/RackPDUs/{PowerDistributionId}/Mains/{CircuitId}</String> |
| <String>/redfish/v1/PowerEquipment/RackPDUs/{PowerDistributionId}/Branches/{CircuitId}</String> |
| <String>/redfish/v1/PowerEquipment/FloorPDUs/{PowerDistributionId}/Mains/{CircuitId}</String> |
| <String>/redfish/v1/PowerEquipment/FloorPDUs/{PowerDistributionId}/Branches/{CircuitId}</String> |
| <String>/redfish/v1/PowerEquipment/FloorPDUs/{PowerDistributionId}/Subfeeds/{CircuitId}</String> |
| <String>/redfish/v1/PowerEquipment/TransferSwitches/{PowerDistributionId}/Mains/{CircuitId}</String> |
| <String>/redfish/v1/PowerEquipment/TransferSwitches/{PowerDistributionId}/Branches/{CircuitId}</String> |
| <String>/redfish/v1/PowerEquipment/TransferSwitches/{PowerDistributionId}/Feeders/{CircuitId}</String> |
| </Collection> |
| </Annotation> |
| </EntityType> |
| |
| <Action Name="PowerControl" IsBound="true"> |
| <Annotation Term="OData.Description" String="This action turns the circuit on or off."/> |
| <Annotation Term="OData.LongDescription" String="This action shall control the power state of the circuit."/> |
| <Parameter Name="Circuit" Type="Circuit.v1_0_0.Actions"/> |
| <Parameter Name="PowerState" Type="Resource.PowerState"> |
| <Annotation Term="OData.Description" String="The desired power state of the circuit."/> |
| <Annotation Term="OData.LongDescription" String="This parameter shall contain the desired power state of the circuit."/> |
| </Parameter> |
| </Action> |
| |
| <Action Name="BreakerControl" IsBound="true"> |
| <Annotation Term="OData.Description" String="This action attempts to reset the circuit breaker."/> |
| <Annotation Term="OData.LongDescription" String="This action shall control the state of the circuit breaker or over-current protection device."/> |
| <Parameter Name="Circuit" Type="Circuit.v1_0_0.Actions"/> |
| <Parameter Name="PowerState" Type="Circuit.PowerState"> |
| <Annotation Term="OData.Description" String="The desired power state of the circuit if the breaker is reset successfully."/> |
| <Annotation Term="OData.LongDescription" String="This parameter shall contain the desired power state of the circuit."/> |
| </Parameter> |
| </Action> |
| |
| <Action Name="ResetMetrics" IsBound="true"> |
| <Annotation Term="OData.Description" String="This action resets metrics related to this circuit."/> |
| <Annotation Term="OData.LongDescription" String="This action shall reset any time intervals or counted values for this circuit."/> |
| <Parameter Name="Circuit" Type="Circuit.v1_0_0.Actions"/> |
| </Action> |
| |
| <EnumType Name="PowerState"> |
| <Member Name="On"> |
| <Annotation Term="OData.Description" String="The circuit is powered on."/> |
| </Member> |
| <Member Name="Off"> |
| <Annotation Term="OData.Description" String="The circuit is powered off."/> |
| </Member> |
| </EnumType> |
| |
| <EnumType Name="BreakerStates"> |
| <Member Name="Normal"> |
| <Annotation Term="OData.Description" String="The breaker is powered on."/> |
| </Member> |
| <Member Name="Tripped"> |
| <Annotation Term="OData.Description" String="The breaker has been tripped."/> |
| </Member> |
| <Member Name="Off"> |
| <Annotation Term="OData.Description" String="The breaker is off."/> |
| </Member> |
| </EnumType> |
| |
| <EnumType Name="PowerRestorePolicyTypes"> |
| <Annotation Term="OData.Description" String="The enumerations of PowerRestorePolicyTypes specify the choice of power state when power is applied."/> |
| <Member Name="AlwaysOn"> |
| <Annotation Term="OData.Description" String="Always power on when external power is applied."/> |
| </Member> |
| <Member Name="AlwaysOff"> |
| <Annotation Term="OData.Description" String="Always remain powered off when external power is applied."/> |
| </Member> |
| <Member Name="LastState"> |
| <Annotation Term="OData.Description" String="Return to the last power state (on or off) when external power is applied."/> |
| </Member> |
| </EnumType> |
| |
| <EnumType Name="PhaseWiringType"> |
| <Member Name="OnePhase3Wire"> |
| <Annotation Term="OData.Description" String="Single-phase / 3-Wire (Line1, Neutral, Protective Earth)."/> |
| <Annotation Term="OData.LongDescription" String="This value shall represent a Single-phase / 3-Wire (Line1, Neutral, Protective Earth) wiring."/> |
| </Member> |
| <Member Name="TwoPhase3Wire"> |
| <Annotation Term="OData.Description" String="Two-phase / 3-Wire (Line1, Line2, Protective Earth)."/> |
| <Annotation Term="OData.LongDescription" String="This value shall represent a Two-phase / 3-Wire (Line1, Line2, Protective Earth) wiring."/> |
| </Member> |
| <Member Name="OneOrTwoPhase3Wire"> |
| <Annotation Term="OData.Description" String="Single or Two-Phase / 3-Wire (Line1, Line2 or Neutral, Protective Earth)."/> |
| <Annotation Term="OData.LongDescription" String="This value shall represent a Single or Two-Phase / 3-Wire (Line1, Line2 or Neutral, Protective Earth) wiring. This value shall be used when both phase configurations are supported. This is most common where detachable cordsets are used."/> |
| </Member> |
| <Member Name="TwoPhase4Wire"> |
| <Annotation Term="OData.Description" String="Two-phase / 4-Wire (Line1, Line2, Neutral, Protective Earth)."/> |
| <Annotation Term="OData.LongDescription" String="This value shall represent a Two-phase / 4-Wire (Line1, Line2, Neutral, Protective Earth) wiring."/> |
| </Member> |
| <Member Name="ThreePhase4Wire"> |
| <Annotation Term="OData.Description" String="Three-phase / 4-Wire (Line1, Line2, Line3, Protective Earth)."/> |
| <Annotation Term="OData.LongDescription" String="This value shall represent a Three-phase / 4-Wire (Line1, Line2, Line3, Protective Earth) wiring."/> |
| </Member> |
| <Member Name="ThreePhase5Wire"> |
| <Annotation Term="OData.Description" String="Three-phase / 5-Wire (Line1, Line2, Line3, Neutral, Protective Earth)."/> |
| <Annotation Term="OData.LongDescription" String="This value shall represent a Three-phase / 5-Wire (Line1, Line2, Line3, Neutral, Protective Earth) wiring."/> |
| </Member> |
| </EnumType> |
| |
| <EnumType Name="NominalVoltageType"> |
| <Member Name="AC100To240V"> |
| <Annotation Term="OData.Description" String="AC 100-240V nominal."/> |
| </Member> |
| <Member Name="AC100To277V"> |
| <Annotation Term="OData.Description" String="AC 100-277V nominal."/> |
| </Member> |
| <Member Name="AC120V"> |
| <Annotation Term="OData.Description" String="AC 120V nominal."/> |
| </Member> |
| <Member Name="AC200To240V"> |
| <Annotation Term="OData.Description" String="AC 200-240V nominal."/> |
| </Member> |
| <Member Name="AC200To277V"> |
| <Annotation Term="OData.Description" String="AC 200-277V nominal."/> |
| </Member> |
| <Member Name="AC208V"> |
| <Annotation Term="OData.Description" String="AC 208V nominal."/> |
| </Member> |
| <Member Name="AC230V"> |
| <Annotation Term="OData.Description" String="AC 230V nominal."/> |
| </Member> |
| <Member Name="AC240V"> |
| <Annotation Term="OData.Description" String="AC 240V nominal."/> |
| </Member> |
| <Member Name="AC240AndDC380V"> |
| <Annotation Term="OData.Description" String="AC 200-240V and DC 380V."/> |
| </Member> |
| <Member Name="AC277V"> |
| <Annotation Term="OData.Description" String="AC 277V nominal."/> |
| </Member> |
| <Member Name="AC277AndDC380V"> |
| <Annotation Term="OData.Description" String="AC 200-277V and DC 380V."/> |
| </Member> |
| <Member Name="AC400V"> |
| <Annotation Term="OData.Description" String="AC 400V or 415V nominal."/> |
| </Member> |
| <Member Name="AC480V"> |
| <Annotation Term="OData.Description" String="AC 480V nominal."/> |
| </Member> |
| <Member Name="DC240V"> |
| <Annotation Term="OData.Description" String="DC 240V nominal."/> |
| </Member> |
| <Member Name="DC380V"> |
| <Annotation Term="OData.Description" String="High Voltage DC (380V)."/> |
| </Member> |
| <Member Name="DCNeg48V"> |
| <Annotation Term="OData.Description" String="-48V DC."/> |
| </Member> |
| </EnumType> |
| |
| <EnumType Name="PlugType"> |
| <Member Name="NEMA_5_15P"> |
| <Annotation Term="OData.Description" String="NEMA 5-15P (Single-phase 125V; 15A; 1P3W)."/> |
| <Annotation Term="OData.LongDescription" String="This value shall represent a plug that matches the NEMA specified 5-15 straight (non-locking) plug (Single-phase 125V; 15A; 1P3W)."/> |
| </Member> |
| <Member Name="NEMA_L5_15P"> |
| <Annotation Term="OData.Description" String="NEMA L5-15P (Single-phase 125V; 15A; 1P3W)."/> |
| <Annotation Term="OData.LongDescription" String="This value shall represent a plug that matches the NEMA specified locking L5-15 plug (Single-phase 125V; 15A; 1P3W)."/> |
| </Member> |
| <Member Name="NEMA_5_20P"> |
| <Annotation Term="OData.Description" String="NEMA 5-20P (Single-phase 125V; 20A; 1P3W)."/> |
| <Annotation Term="OData.LongDescription" String="This value shall represent a plug that matches the NEMA specified 5-20 straight (non-locking) plug that exhibits a T-slot (Single-phase 125V; 20A; 1P3W)."/> |
| </Member> |
| <Member Name="NEMA_L5_20P"> |
| <Annotation Term="OData.Description" String="NEMA L5-20P (Single-phase 125V; 20A; 1P3W)."/> |
| <Annotation Term="OData.LongDescription" String="This value shall represent a plug that matches the NEMA specified locking L5-20 plug (Single-phase 125V; 20A; 1P3W)."/> |
| </Member> |
| <Member Name="NEMA_L5_30P"> |
| <Annotation Term="OData.Description" String="NEMA L5-30P (Single-phase 125V; 30A; 1P3W)."/> |
| <Annotation Term="OData.LongDescription" String="This value shall represent a plug that matches the NEMA specified locking L5-30 plug (Single-phase 125V; 30A; 1P3W)."/> |
| </Member> |
| <Member Name="NEMA_6_15P"> |
| <Annotation Term="OData.Description" String="NEMA 6-15P (Single-phase 250V; 15A; 2P3W)."/> |
| <Annotation Term="OData.LongDescription" String="This value shall represent a plug that matches the NEMA specified 6-15 straight (non-locking) plug (Single-phase 250V; 15A; 2P3W)."/> |
| </Member> |
| <Member Name="NEMA_L6_15P"> |
| <Annotation Term="OData.Description" String="NEMA L6-15P (Single-phase 250V; 15A; 2P3W)."/> |
| <Annotation Term="OData.LongDescription" String="This value shall represent a plug that matches the NEMA specified locking L6-15 plug (Single-phase 250V; 15A; 2P3W)."/> |
| </Member> |
| <Member Name="NEMA_6_20P"> |
| <Annotation Term="OData.Description" String="NEMA 6-20P (Single-phase 250V; 20A; 2P3W)."/> |
| <Annotation Term="OData.LongDescription" String="This value shall represent a plug that matches the NEMA specified 6-20 straight (non-locking) plug (Single-phase 250V; 20A; 2P3W)."/> |
| </Member> |
| <Member Name="NEMA_L6_20P"> |
| <Annotation Term="OData.Description" String="NEMA L6-20P (Single-phase 250V; 20A; 2P3W)."/> |
| <Annotation Term="OData.LongDescription" String="This value shall represent a plug that matches the NEMA specified locking L6-20 plug (Single-phase 250V; 20A; 2P3W)."/> |
| </Member> |
| <Member Name="NEMA_L6_30P"> |
| <Annotation Term="OData.Description" String="NEMA L6-30P (Single-phase 250V; 30A; 2P3W)."/> |
| <Annotation Term="OData.LongDescription" String="This value shall represent a plug that matches the NEMA specified locking L6-30 plug (Single-phase 250V; 30A; 2P3W)."/> |
| </Member> |
| <Member Name="NEMA_L14_20P"> |
| <Annotation Term="OData.Description" String="NEMA L14-20P (Split-phase 125/250V; 20A; 2P4W)."/> |
| <Annotation Term="OData.LongDescription" String="This value shall represent a plug that matches the NEMA specified locking L14-20 plug (Split-phase 125/250V; 20A; 2P4W)."/> |
| </Member> |
| <Member Name="NEMA_L14_30P"> |
| <Annotation Term="OData.Description" String="NEMA L14-30P (Split-phase 125/250V; 30A; 2P4W)."/> |
| <Annotation Term="OData.LongDescription" String="This value shall represent a plug that matches the NEMA specified locking L14-30 plug (Split-phase 125/250V; 30A; 2P4W)."/> |
| </Member> |
| <Member Name="NEMA_L15_20P"> |
| <Annotation Term="OData.Description" String="NEMA L15-20P (Three-phase 250V; 20A; 3P4W)."/> |
| <Annotation Term="OData.LongDescription" String="This value shall represent a plug that matches the NEMA specified locking L15-20 plug (Three-phase 250V; 20A; 3P4W)."/> |
| </Member> |
| <Member Name="NEMA_L15_30P"> |
| <Annotation Term="OData.Description" String="NEMA L15-30P (Three-phase 250V; 30A; 3P4W)."/> |
| <Annotation Term="OData.LongDescription" String="This value shall represent a plug that matches the NEMA specified locking L15-30 plug (Three-phase 250V; 30A; 3P4W)."/> |
| </Member> |
| <Member Name="NEMA_L21_20P"> |
| <Annotation Term="OData.Description" String="NEMA L21-20P (Three-phase 120/208V; 20A; 3P5W)."/> |
| <Annotation Term="OData.LongDescription" String="This value shall represent a plug that matches the NEMA specified locking L21-20 plug (Three-phase 120/208V; 20A; 3P5W)."/> |
| </Member> |
| <Member Name="NEMA_L21_30P"> |
| <Annotation Term="OData.Description" String="NEMA L21-30P (Three-phase 120/208V; 30A; 3P5W)."/> |
| <Annotation Term="OData.LongDescription" String="This value shall represent a plug that matches the NEMA specified locking L21-30 plug (Three-phase 120/208V; 30A; 3P5W)."/> |
| </Member> |
| <Member Name="NEMA_L22_20P"> |
| <Annotation Term="OData.Description" String="NEMA L22-20P (Three-phase 277/480V; 20A; 3P5W)."/> |
| <Annotation Term="OData.LongDescription" String="This value shall represent a plug that matches the NEMA specified locking L22-20 plug (Three-phase 277/480V; 20A; 3P5W)."/> |
| </Member> |
| <Member Name="NEMA_L22_30P"> |
| <Annotation Term="OData.Description" String="NEMA L22-30P (Three-phase 277/480V; 30A; 3P5W)."/> |
| <Annotation Term="OData.LongDescription" String="This value shall represent a plug that matches the NEMA specified locking L22-30 plug (Three-phase 277/480V; 30A; 3P5W)."/> |
| </Member> |
| <Member Name="California_CS8265"> |
| <Annotation Term="OData.Description" String="California Standard CS8265 (Single-phase 250V; 50A; 2P3W)."/> |
| <Annotation Term="OData.LongDescription" String="This value shall represent a plug that matches the 'California Standard' CS8265 style plug (Three-phase 250V; 50A; 3P4W)."/> |
| </Member> |
| <Member Name="California_CS8365"> |
| <Annotation Term="OData.Description" String="California Standard CS8365 (Three-phase 250V; 50A; 3P4W)."/> |
| <Annotation Term="OData.LongDescription" String="This value shall represent a plug that matches the 'California Standard' CS8365 style plug (Three-phase 250V; 50A; 3P4W)."/> |
| </Member> |
| <Member Name="IEC_60320_C14"> |
| <Annotation Term="OData.Description" String="IEC C14 (Single-phase 250V; 10A; 1P3W)."/> |
| <Annotation Term="OData.LongDescription" String="This value shall represent a plug that matches the IEC 60320 specified C14 input (Single-phase 250V; 10A; 1P3W)."/> |
| </Member> |
| <Member Name="IEC_60320_C20"> |
| <Annotation Term="OData.Description" String="IEC C20 (Single-phase 250V; 16A; 1P3W)."/> |
| <Annotation Term="OData.LongDescription" String="This value shall represent a plug that matches the IEC 60320 specified C20 input (Single-phase 250V; 16A; 1P3W)."/> |
| </Member> |
| <Member Name="IEC_60309_316P6"> |
| <Annotation Term="OData.Description" String="IEC 60309 316P6 (Single-phase 200-250V; 16A; 1P3W; Blue, 6-hour)."/> |
| <Annotation Term="OData.LongDescription" String="This value shall represent a plug that matches the IEC 60309 316P6 plug (Single-phase 200-250V; 16A; 1P3W; Blue, 6-hour)."/> |
| </Member> |
| <Member Name="IEC_60309_332P6"> |
| <Annotation Term="OData.Description" String="IEC 60309 332P6 (Single-phase 200-250V; 32A; 1P3W; Blue, 6-hour)."/> |
| <Annotation Term="OData.LongDescription" String="This value shall represent a plug that matches the IEC 60309 332P6 plug (Single-phase 200-250V; 32A; 1P3W; Blue, 6-hour)."/> |
| </Member> |
| <Member Name="IEC_60309_363P6"> |
| <Annotation Term="OData.Description" String="IEC 60309 363P6 (Single-phase 200-250V; 63A; 1P3W; Blue, 6-hour)."/> |
| <Annotation Term="OData.LongDescription" String="This value shall represent a plug that matches the IEC 60309 363P6 plug (Single-phase 200-250V; 63A; 1P3W; Blue, 6-hour)."/> |
| </Member> |
| <Member Name="IEC_60309_516P6"> |
| <Annotation Term="OData.Description" String="IEC 60309 516P6 (Three-phase 200-240/346-415V; 16A; 3P5W; Red; 6-hour)."/> |
| <Annotation Term="OData.LongDescription" String="This value shall represent a plug that matches the IEC 60309 516P6 plug (Three-phase 200-240/346-415V; 16A; 3P5W; Red; 6-hour)."/> |
| </Member> |
| <Member Name="IEC_60309_532P6"> |
| <Annotation Term="OData.Description" String="IEC 60309 532P6 (Three-phase 200-240/346-415V; 32A; 3P5W; Red; 6-hour)."/> |
| <Annotation Term="OData.LongDescription" String="This value shall represent a plug that matches the IEC 60309 plug 532P6 (Three-phase 200-240/346-415V; 32A; 3P5W; Red; 6-hour)."/> |
| </Member> |
| <Member Name="IEC_60309_563P6"> |
| <Annotation Term="OData.Description" String="IEC 60309 563P6 (Three-phase 200-240/346-415V; 63A; 3P5W; Red; 6-hour)."/> |
| <Annotation Term="OData.LongDescription" String="This value shall represent a plug that matches the IEC 60309 563P6 plug (Three-phase 200-240/346-415V; 63A; 3P5W; Red; 6-hour)."/> |
| </Member> |
| <Member Name="IEC_60309_460P9"> |
| <Annotation Term="OData.Description" String="IEC 60309 460P9 (Three-phase 200-250V; 60A; 3P4W; Blue; 9-hour)."/> |
| <Annotation Term="OData.LongDescription" String="This value shall represent a plug that matches the IEC 60309 460P9 plug (Three-phase 200-250V; 60A; 3P4W; Blue; 9-hour)."/> |
| </Member> |
| <Member Name="IEC_60309_560P9"> |
| <Annotation Term="OData.Description" String="IEC 60309 560P9 (Three-phase 120-144/208-250V; 60A; 3P5W; Blue; 9-hour)."/> |
| <Annotation Term="OData.LongDescription" String="This value shall represent a plug that matches the IEC 60309 plug 560P9 (Three-phase 120-144/208-250V; 60A; 3P5W; Blue; 9-hour)."/> |
| </Member> |
| <Member Name="Field_208V_3P4W_60A"> |
| <Annotation Term="OData.Description" String="Field-wired; Three-phase 200-250V; 60A; 3P4W."/> |
| <Annotation Term="OData.LongDescription" String="This value shall represent field-wired input is three-phase 200-250V; 60A; 3P4W. It is appropriate for use on a 60A branch circuit."/> |
| </Member> |
| <Member Name="Field_400V_3P5W_32A"> |
| <Annotation Term="OData.Description" String="Field-wired; Three-phase 200-240/346-415V; 32A; 3P5W."/> |
| <Annotation Term="OData.LongDescription" String="This value shall represent field-wired input is three-phase 200-240/346-415V; 32A; 3P5W. It is appropriate for use on a 30, 32A, or 40A branch circuit."/> |
| </Member> |
| </EnumType> |
| </Schema> |
| |
| <Schema xmlns="http://docs.oasis-open.org/odata/ns/edm" Namespace="Circuit.v1_0_0"> |
| <Annotation Term="Redfish.OwningEntity" String="DMTF"/> |
| <Annotation Term="Redfish.Release" String="2019.4"/> |
| <EntityType Name="Circuit" BaseType="Circuit.Circuit"> |
| <Property Name="Status" Type="Resource.Status" Nullable="false"> |
| <Annotation Term="OData.Description" String="The status and health of the resource and its subordinate or dependent resources."/> |
| <Annotation Term="OData.LongDescription" String="This property shall contain any status or health properties of the resource."/> |
| </Property> |
| <Property Name="CircuitType" Type="Circuit.v1_0_0.CircuitType"> |
| <Annotation Term="OData.Permissions" EnumMember="OData.Permission/Read"/> |
| <Annotation Term="OData.Description" String="The type of circuit."/> |
| <Annotation Term="OData.LongDescription" String="This property shall contain the type of circuit."/> |
| </Property> |
| <Property Name="CriticalCircuit" Type="Edm.Boolean"> |
| <Annotation Term="OData.Permissions" EnumMember="OData.Permission/ReadWrite"/> |
| <Annotation Term="OData.Description" String="Designates if this is a critical circuit."/> |
| <Annotation Term="OData.LongDescription" String="This property shall indicate whether the circuit is desginated as a critical circuit, and therefore is excluded from autonomous logic that could affect the state of the circuit. The value shall be `true` if the circuit is deemed critical, and `false` if the circuit is not critical."/> |
| </Property> |
| <Property Name="ElectricalContext" Type="Sensor.ElectricalContext"> |
| <Annotation Term="OData.Permissions" EnumMember="OData.Permission/Read"/> |
| <Annotation Term="OData.Description" String="The combination of current-carrying conductors."/> |
| <Annotation Term="OData.LongDescription" String="This property shall contain the combination of current-carrying conductors that distribute power."/> |
| </Property> |
| <Property Name="PhaseWiringType" Type="Circuit.PhaseWiringType"> |
| <Annotation Term="OData.Permissions" EnumMember="OData.Permission/Read"/> |
| <Annotation Term="OData.Description" String="The number of ungrounded current-carrying conductors (phases) and the total number of conductors (wires)."/> |
| <Annotation Term="OData.LongDescription" String="This property shall contain the number of ungrounded current-carrying conductors (phases) and the total number of conductors (wires)."/> |
| </Property> |
| <Property Name="VoltageType" Type="Circuit.v1_0_0.VoltageType"> |
| <Annotation Term="OData.Permissions" EnumMember="OData.Permission/Read"/> |
| <Annotation Term="OData.Description" String="The type of voltage applied to the circuit."/> |
| <Annotation Term="OData.LongDescription" String="This property shall contain the type of voltage applied to the circuit."/> |
| </Property> |
| <Property Name="PlugType" Type="Circuit.PlugType"> |
| <Annotation Term="OData.Permissions" EnumMember="OData.Permission/Read"/> |
| <Annotation Term="OData.Description" String="The type of plug according to NEMA, IEC, or regional standards."/> |
| <Annotation Term="OData.LongDescription" String="This property shall contain the type of physical plug used for this circuit, as defined by IEC, NEMA, or regional standard."/> |
| </Property> |
| <Property Name="NominalVoltage" Type="Circuit.NominalVoltageType"> |
| <Annotation Term="OData.Permissions" EnumMember="OData.Permission/Read"/> |
| <Annotation Term="OData.Description" String="The nominal voltage for this circuit."/> |
| <Annotation Term="OData.LongDescription" String="This property shall contain the nominal voltage for this circuit, in Volts."/> |
| </Property> |
| <Property Name="RatedCurrentAmps" Type="Edm.Decimal"> |
| <Annotation Term="OData.Permissions" EnumMember="OData.Permission/Read"/> |
| <Annotation Term="OData.Description" String="The rated maximum current allowed for this circuit."/> |
| <Annotation Term="OData.LongDescription" String="This property shall contain the rated maximum current for this circuit, in Amps, after any required de-rating, due to safety agency or other regulatory requirements, has been applied."/> |
| <Annotation Term="Measures.Unit" String="A"/> |
| <Annotation Term="Validation.Minimum" Int="0"/> |
| </Property> |
| <Property Name="IndicatorLED" Type="Resource.IndicatorLED"> |
| <Annotation Term="OData.Permissions" EnumMember="OData.Permission/ReadWrite"/> |
| <Annotation Term="OData.Description" String="The state of the indicator LED, which identifies the circuit."/> |
| <Annotation Term="OData.LongDescription" String="This property shall contain the indicator light state for the indicator light associated with this circuit."/> |
| </Property> |
| <Property Name="BreakerState" Type="Circuit.BreakerStates"> |
| <Annotation Term="OData.Permissions" EnumMember="OData.Permission/Read"/> |
| <Annotation Term="OData.Description" String="The state of the over current protection device."/> |
| <Annotation Term="OData.LongDescription" String="This property shall contain the state of the over current protection device."/> |
| </Property> |
| <Property Name="PowerOnDelaySeconds" Type="Edm.Decimal"> |
| <Annotation Term="OData.Permissions" EnumMember="OData.Permission/ReadWrite"/> |
| <Annotation Term="OData.Description" String="The number of seconds to delay power up after a power cycle or a PowerControl action. Zero seconds indicates no delay to power up."/> |
| <Annotation Term="OData.LongDescription" String="This property shall contain the number of seconds to delay power up after a power cycle or a PowerControl action. The value `0` shall indicate no delay to power up."/> |
| </Property> |
| <Property Name="PowerOffDelaySeconds" Type="Edm.Decimal"> |
| <Annotation Term="OData.Permissions" EnumMember="OData.Permission/ReadWrite"/> |
| <Annotation Term="OData.Description" String="The number of seconds to delay power off after a PowerControl action. Zero seconds indicates no delay to power off."/> |
| <Annotation Term="OData.LongDescription" String="This property shall contain the number of seconds to delay power off after a PowerControl action. The value `0` shall indicate no delay to power off."/> |
| </Property> |
| <Property Name="PowerCycleDelaySeconds" Type="Edm.Decimal"> |
| <Annotation Term="OData.Permissions" EnumMember="OData.Permission/ReadWrite"/> |
| <Annotation Term="OData.Description" String="The number of seconds to delay power on after a PowerControl action to cycle power. Zero seconds indicates no delay."/> |
| <Annotation Term="OData.LongDescription" String="This property shall contain the number of seconds to delay power on after a PowerControl action to cycle power. The value `0` shall indicate no delay to power on."/> |
| </Property> |
| <Property Name="PowerRestoreDelaySeconds" Type="Edm.Decimal"> |
| <Annotation Term="OData.Permissions" EnumMember="OData.Permission/ReadWrite"/> |
| <Annotation Term="OData.Description" String="The number of seconds to delay power on after power has been restored. Zero seconds indicates no delay."/> |
| <Annotation Term="OData.LongDescription" String="This property shall contain the number of seconds to delay power on after a power fault. The value `0` shall indicate no delay to power on."/> |
| </Property> |
| <Property Name="PowerRestorePolicy" Type="Circuit.PowerRestorePolicyTypes" Nullable="false"> |
| <Annotation Term="OData.Permissions" EnumMember="OData.Permission/ReadWrite"/> |
| <Annotation Term="OData.Description" String="The desired power state of the circuit when power is restored after a power loss."/> |
| <Annotation Term="OData.LongDescription" String="This property shall contain the desired PowerState of the circuit when power is applied. The value `LastState` shall return the circuit to the PowerState it was in when power was lost."/> |
| </Property> |
| <Property Name="PowerState" Type="Resource.PowerState"> |
| <Annotation Term="OData.Permissions" EnumMember="OData.Permission/Read"/> |
| <Annotation Term="OData.Description" String="The power state of the circuit."/> |
| <Annotation Term="OData.LongDescription" String="This property shall contain the power state of the circuit."/> |
| </Property> |
| <Property Name="PowerEnabled" Type="Edm.Boolean"> |
| <Annotation Term="OData.Permissions" EnumMember="OData.Permission/Read"/> |
| <Annotation Term="OData.Description" String="Indicates if the circuit can be powered."/> |
| <Annotation Term="OData.LongDescription" String="This property shall indicate the power enable state of the circuit. The value `true` shall indicate that the circuit can be powered on, and `false` shall indicate that the circuit cannot be powered."/> |
| </Property> |
| <NavigationProperty Name="Voltage" Type="Sensor.Sensor"> |
| <Annotation Term="OData.Permissions" EnumMember="OData.Permission/Read"/> |
| <Annotation Term="Redfish.ExcerptCopy" String="Voltage"/> |
| <Annotation Term="OData.Description" String="The voltage reading for this single phase circuit."/> |
| <Annotation Term="OData.LongDescription" String="This property shall contain the voltage, measured in Volts, for this single phase circuit. This property shall not appear in resource instances representing poly-phase circuits."/> |
| </NavigationProperty> |
| <NavigationProperty Name="CurrentAmps" Type="Sensor.Sensor"> |
| <Annotation Term="OData.Permissions" EnumMember="OData.Permission/Read"/> |
| <Annotation Term="Redfish.ExcerptCopy" String="Current"/> |
| <Annotation Term="OData.Description" String="The current reading for this single phase circuit."/> |
| <Annotation Term="OData.LongDescription" String="This property shall contain the current, measured in Amperes, for this single phase circuit. This property shall not appear in resource instances representing poly-phase circuits."/> |
| </NavigationProperty> |
| <NavigationProperty Name="PowerWatts" Type="Sensor.Sensor"> |
| <Annotation Term="OData.Permissions" EnumMember="OData.Permission/Read"/> |
| <Annotation Term="Redfish.ExcerptCopy" String="Power"/> |
| <Annotation Term="OData.Description" String="The power reading for this circuit."/> |
| <Annotation Term="OData.LongDescription" String="This property shall contain the total power, measured in Watts, for this circuit, that represents the `Total` ElectricalContext sensor when multiple power sensors exist for this circuit."/> |
| </NavigationProperty> |
| <NavigationProperty Name="EnergykWh" Type="Sensor.Sensor"> |
| <Annotation Term="OData.Permissions" EnumMember="OData.Permission/Read"/> |
| <Annotation Term="Redfish.ExcerptCopy" String="EnergykWh"/> |
| <Annotation Term="OData.Description" String="The energy reading for this circuit."/> |
| <Annotation Term="OData.LongDescription" String="This property shall contain the total energy, measured in kilowatt-hours (kW.h), for this circuit, that represents the `Total` ElectricalContext sensor when multiple energy sensors exist for this circuit."/> |
| </NavigationProperty> |
| <NavigationProperty Name="FrequencyHz" Type="Sensor.Sensor"> |
| <Annotation Term="OData.Permissions" EnumMember="OData.Permission/Read"/> |
| <Annotation Term="Redfish.ExcerptCopy"/> |
| <Annotation Term="OData.Description" String="The frequency reading for this circuit."/> |
| <Annotation Term="OData.LongDescription" String="This property shall contain the frequency sensor for this circuit."/> |
| </NavigationProperty> |
| <Property Name="PolyPhaseVoltage" Type="Circuit.v1_0_0.VoltageSensors"> |
| <Annotation Term="OData.Description" String="The voltage readings for this circuit."/> |
| <Annotation Term="OData.LongDescription" String="This property shall contain the voltage sensor(s) for this circuit. For single phase circuits this property shall contain a duplicate copy of the voltage sensor referenced in the VoltageSensor property, if present. For poly-phase circuits this property should contain multiple voltage sensor readings used to fully describe the circuit."/> |
| </Property> |
| <Property Name="PolyPhaseCurrentAmps" Type="Circuit.v1_0_0.CurrentSensors"> |
| <Annotation Term="OData.Description" String="The current readings for this circuit."/> |
| <Annotation Term="OData.LongDescription" String="This property shall contain the current sensor(s) for this circuit. For single phase circuits this property shall contain a duplicate copy of the current sensor referenced in the CurrentSensor property, if present. For poly-phase circuits this property should contain multiple current sensor readings used to fully describe the circuit."/> |
| </Property> |
| <Property Name="PolyPhasePowerWatts" Type="Circuit.v1_0_0.PowerSensors"> |
| <Annotation Term="OData.Description" String="The power readings for this circuit."/> |
| <Annotation Term="OData.LongDescription" String="This property shall contain the power sensor(s) for this circuit. For single phase circuits this property shall contain a duplicate copy of the power sensor referenced in the PowerSensor property, if present. For poly-phase circuits this property should contain multiple power sensor readings used to fully describe the circuit."/> |
| </Property> |
| <Property Name="PolyPhaseEnergykWh" Type="Circuit.v1_0_0.EnergySensors"> |
| <Annotation Term="OData.Description" String="The energy readings for this circuit."/> |
| <Annotation Term="OData.LongDescription" String="This property shall contain the energy sensor(s) for this circuit. For single phase circuits this property shall contain a duplicate copy of the energy sensor referenced in the EnergySensor property, if present. For poly-phase circuits this property should contain multiple energy sensor readings used to fully describe the circuit."/> |
| </Property> |
| <Property Name="Links" Type="Circuit.v1_0_0.Links" Nullable="false"> |
| <Annotation Term="OData.Description" String="The links to other resources that are related to this resource."/> |
| <Annotation Term="OData.LongDescription" String="This property shall contain links to resources that are related to but are not contained by, or subordinate to, this resource."/> |
| </Property> |
| <Property Name="Actions" Type="Circuit.v1_0_0.Actions" Nullable="false"> |
| <Annotation Term="OData.Description" String="The available actions for this resource."/> |
| <Annotation Term="OData.LongDescription" String="This property shall contain the available actions for this resource."/> |
| </Property> |
| </EntityType> |
| |
| <ComplexType Name="Links" BaseType="Resource.Links"> |
| <Annotation Term="OData.Description" String="The links to other resources that are related to this resource."/> |
| <Annotation Term="OData.LongDescription" String="This Redfish Specification-described type shall contain links to resources that are related to but are not contained by, or subordinate to, this resource."/> |
| <NavigationProperty Name="BranchCircuit" Type="Circuit.Circuit"> |
| <Annotation Term="OData.Permissions" EnumMember="OData.Permission/Read"/> |
| <Annotation Term="OData.Description" String="A reference to the branch circuit related to this circuit."/> |
| <Annotation Term="OData.LongDescription" String="This property shall contain a link to a resource of type Circuit that represents the branch circuit associated with this circuit."/> |
| <Annotation Term="OData.AutoExpandReferences"/> |
| </NavigationProperty> |
| <NavigationProperty Name="Outlets" Type="Collection(Outlet.Outlet)"> |
| <Annotation Term="OData.Permissions" EnumMember="OData.Permission/Read"/> |
| <Annotation Term="OData.Description" String="An array of references to the outlets contained by this circuit."/> |
| <Annotation Term="OData.LongDescription" String="This property shall contain an array of links to resources of type Outlet that represent the outlets associated with this circuit."/> |
| <Annotation Term="OData.AutoExpandReferences"/> |
| </NavigationProperty> |
| </ComplexType> |
| |
| <ComplexType Name="Actions"> |
| <Annotation Term="OData.AdditionalProperties" Bool="false"/> |
| <Annotation Term="OData.Description" String="The available actions for this resource."/> |
| <Annotation Term="OData.LongDescription" String="This type shall contain the available actions for this resource."/> |
| <Property Name="Oem" Type="Circuit.v1_0_0.OemActions" Nullable="false"> |
| <Annotation Term="OData.Description" String="The available OEM-specific actions for this resource."/> |
| <Annotation Term="OData.LongDescription" String="This property shall contain the available OEM-specific actions for this resource."/> |
| </Property> |
| </ComplexType> |
| |
| <ComplexType Name="OemActions"> |
| <Annotation Term="OData.AdditionalProperties" Bool="true"/> |
| <Annotation Term="OData.Description" String="The available OEM-specific actions for this resource."/> |
| <Annotation Term="OData.LongDescription" String="This type shall contain the available OEM-specific actions for this resource."/> |
| </ComplexType> |
| |
| <ComplexType Name="VoltageSensors"> |
| <Annotation Term="OData.AdditionalProperties" Bool="false"/> |
| <Annotation Term="OData.Description" String="The voltage readings for this circuit."/> |
| <Annotation Term="OData.LongDescription" String="This type shall contain properties that describe voltage sensor readings for a circuit."/> |
| <NavigationProperty Name="Line1ToLine2" Type="Sensor.Sensor"> |
| <Annotation Term="OData.Permissions" EnumMember="OData.Permission/Read"/> |
| <Annotation Term="Redfish.ExcerptCopy" String="Voltage"/> |
| <Annotation Term="OData.Description" String="The Line 1 to Line 2 voltage reading for this circuit."/> |
| <Annotation Term="OData.LongDescription" String="This property shall contain a VoltageSensor excerpt that measures voltage between L1 and L2. This property shall not be present if the circuit does not include an L1-L2 measurement."/> |
| </NavigationProperty> |
| <NavigationProperty Name="Line2ToLine3" Type="Sensor.Sensor"> |
| <Annotation Term="OData.Permissions" EnumMember="OData.Permission/Read"/> |
| <Annotation Term="Redfish.ExcerptCopy" String="Voltage"/> |
| <Annotation Term="OData.Description" String="The Line 2 to Line 3 voltage reading for this circuit."/> |
| <Annotation Term="OData.LongDescription" String="This property shall contain a VoltageSensor excerpt that measures voltage between L2 and L3. This property shall not be present if the circuit does not include an L2-L3 measurement."/> |
| </NavigationProperty> |
| <NavigationProperty Name="Line3ToLine1" Type="Sensor.Sensor"> |
| <Annotation Term="OData.Permissions" EnumMember="OData.Permission/Read"/> |
| <Annotation Term="Redfish.ExcerptCopy" String="Voltage"/> |
| <Annotation Term="OData.Description" String="The Line 3 to Line 1 voltage reading for this circuit."/> |
| <Annotation Term="OData.LongDescription" String="This property shall contain a VoltageSensor excerpt that measures voltage between L3 and L1. This property shall not be present if the circuit does not include an L3-L1 measurement."/> |
| </NavigationProperty> |
| <NavigationProperty Name="Line1ToNeutral" Type="Sensor.Sensor"> |
| <Annotation Term="OData.Permissions" EnumMember="OData.Permission/Read"/> |
| <Annotation Term="Redfish.ExcerptCopy" String="Voltage"/> |
| <Annotation Term="OData.Description" String="The Line 1 to Neutral voltage reading for this circuit."/> |
| <Annotation Term="OData.LongDescription" String="This property shall contain a VoltageSensor excerpt that measures voltage between L1 and Neutral. This property shall not be present if the circuit does not include an L1-Neutral measurement."/> |
| </NavigationProperty> |
| <NavigationProperty Name="Line2ToNeutral" Type="Sensor.Sensor"> |
| <Annotation Term="OData.Permissions" EnumMember="OData.Permission/Read"/> |
| <Annotation Term="Redfish.ExcerptCopy" String="Voltage"/> |
| <Annotation Term="OData.Description" String="The Line 2 to Neutral voltage reading for this circuit."/> |
| <Annotation Term="OData.LongDescription" String="This property shall contain a VoltageSensor excerpt that measures voltage between L2 and Neutral. This property shall not be present if the circuit does not include an L2-Neutral measurement."/> |
| </NavigationProperty> |
| <NavigationProperty Name="Line3ToNeutral" Type="Sensor.Sensor"> |
| <Annotation Term="OData.Permissions" EnumMember="OData.Permission/Read"/> |
| <Annotation Term="Redfish.ExcerptCopy" String="Voltage"/> |
| <Annotation Term="OData.Description" String="The Line 3 to Neutral voltage reading for this circuit."/> |
| <Annotation Term="OData.LongDescription" String="This property shall contain a VoltageSensor excerpt that measures voltage between L3 and Neutral. This property shall not be present if the circuit does not include an L3-Neutral measurement."/> |
| </NavigationProperty> |
| </ComplexType> |
| |
| <ComplexType Name="CurrentSensors"> |
| <Annotation Term="OData.AdditionalProperties" Bool="false"/> |
| <Annotation Term="OData.Description" String="The current sensors for this circuit."/> |
| <Annotation Term="OData.LongDescription" String="This type shall contain properties that describe current sensor readings for a circuit."/> |
| <NavigationProperty Name="Line1" Type="Sensor.Sensor"> |
| <Annotation Term="OData.Permissions" EnumMember="OData.Permission/Read"/> |
| <Annotation Term="Redfish.ExcerptCopy" String="Current"/> |
| <Annotation Term="OData.Description" String="Line 1 current sensor."/> |
| <Annotation Term="OData.LongDescription" String="This property shall contain a CurrentSensor excerpt that measures current for L1. This property shall not be present if the circuit does not include an L1 measurement."/> |
| </NavigationProperty> |
| <NavigationProperty Name="Line2" Type="Sensor.Sensor"> |
| <Annotation Term="OData.Permissions" EnumMember="OData.Permission/Read"/> |
| <Annotation Term="Redfish.ExcerptCopy" String="Current"/> |
| <Annotation Term="OData.Description" String="Line 2 current sensor."/> |
| <Annotation Term="OData.LongDescription" String="This property shall contain a CurrentSensor excerpt that measures current for L2. This property shall not be present if the circuit does not include an L2 measurement."/> |
| </NavigationProperty> |
| <NavigationProperty Name="Line3" Type="Sensor.Sensor"> |
| <Annotation Term="OData.Permissions" EnumMember="OData.Permission/Read"/> |
| <Annotation Term="Redfish.ExcerptCopy" String="Current"/> |
| <Annotation Term="OData.Description" String="Line 3 current sensor."/> |
| <Annotation Term="OData.LongDescription" String="This property shall contain a CurrentSensor excerpt that measures current for L3. This property shall not be present if the circuit does not include an L3 measurement."/> |
| </NavigationProperty> |
| <NavigationProperty Name="Neutral" Type="Sensor.Sensor"> |
| <Annotation Term="OData.Permissions" EnumMember="OData.Permission/Read"/> |
| <Annotation Term="Redfish.ExcerptCopy" String="Current"/> |
| <Annotation Term="OData.Description" String="Neutral line current sensor."/> |
| <Annotation Term="OData.LongDescription" String="This property shall contain a CurrentSensor excerpt that measures current for the Neutral line. This property shall not be present if the circuit does not include a Neutral measurement."/> |
| </NavigationProperty> |
| </ComplexType> |
| |
| <ComplexType Name="EnergySensors"> |
| <Annotation Term="OData.AdditionalProperties" Bool="false"/> |
| <Annotation Term="OData.Description" String="The energy readings for this circuit."/> |
| <Annotation Term="OData.LongDescription" String="This type shall contain properties that describe energy sensor readings for a circuit."/> |
| <NavigationProperty Name="Line1ToLine2" Type="Sensor.Sensor"> |
| <Annotation Term="OData.Permissions" EnumMember="OData.Permission/Read"/> |
| <Annotation Term="Redfish.ExcerptCopy" String="EnergykWh"/> |
| <Annotation Term="OData.Description" String="The Line 1 to Line 2 energy reading for this circuit."/> |
| <Annotation Term="OData.LongDescription" String="This property shall contain a EnergykWhSensor excerpt that measures energy between L1 and L2. This property shall not be present if the circuit does not include an L1-L2 measurement."/> |
| </NavigationProperty> |
| <NavigationProperty Name="Line2ToLine3" Type="Sensor.Sensor"> |
| <Annotation Term="OData.Permissions" EnumMember="OData.Permission/Read"/> |
| <Annotation Term="Redfish.ExcerptCopy" String="EnergykWh"/> |
| <Annotation Term="OData.Description" String="The Line 2 to Line 3 energy reading for this circuit."/> |
| <Annotation Term="OData.LongDescription" String="This property shall contain a EnergykWhSensor excerpt that measures energy between L2 and L3. This property shall not be present if the circuit does not include an L2-L3 measurement."/> |
| </NavigationProperty> |
| <NavigationProperty Name="Line3ToLine1" Type="Sensor.Sensor"> |
| <Annotation Term="OData.Permissions" EnumMember="OData.Permission/Read"/> |
| <Annotation Term="Redfish.ExcerptCopy" String="EnergykWh"/> |
| <Annotation Term="OData.Description" String="The Line 3 to Line 1 energy reading for this circuit."/> |
| <Annotation Term="OData.LongDescription" String="This property shall contain a EnergykWhSensor excerpt that measures energy between L3 and L1. This property shall not be present if the circuit does not include an L3-L1 measurement."/> |
| </NavigationProperty> |
| <NavigationProperty Name="Line1ToNeutral" Type="Sensor.Sensor"> |
| <Annotation Term="OData.Permissions" EnumMember="OData.Permission/Read"/> |
| <Annotation Term="Redfish.ExcerptCopy" String="EnergykWh"/> |
| <Annotation Term="OData.Description" String="The Line 1 to Neutral energy reading for this circuit."/> |
| <Annotation Term="OData.LongDescription" String="This property shall contain a EnergykWhSensor excerpt that measures energy between L1 and Neutral. This property shall not be present if the circuit does not include an L1-Neutral measurement."/> |
| </NavigationProperty> |
| <NavigationProperty Name="Line2ToNeutral" Type="Sensor.Sensor"> |
| <Annotation Term="OData.Permissions" EnumMember="OData.Permission/Read"/> |
| <Annotation Term="Redfish.ExcerptCopy" String="EnergykWh"/> |
| <Annotation Term="OData.Description" String="The Line 2 to Neutral energy reading for this circuit."/> |
| <Annotation Term="OData.LongDescription" String="This property shall contain a EnergykWhSensor excerpt that measures energy between L2 and Neutral. This property shall not be present if the circuit does not include an L2-Neutral measurement."/> |
| </NavigationProperty> |
| <NavigationProperty Name="Line3ToNeutral" Type="Sensor.Sensor"> |
| <Annotation Term="OData.Permissions" EnumMember="OData.Permission/Read"/> |
| <Annotation Term="Redfish.ExcerptCopy" String="EnergykWh"/> |
| <Annotation Term="OData.Description" String="The Line 3 to Neutral energy reading for this circuit."/> |
| <Annotation Term="OData.LongDescription" String="This property shall contain a EnergykWhSensor excerpt that measures energy between L3 and Neutral. This property shall not be present if the circuit does not include an L3-Neutral measurement."/> |
| </NavigationProperty> |
| </ComplexType> |
| |
| <ComplexType Name="PowerSensors"> |
| <Annotation Term="OData.AdditionalProperties" Bool="false"/> |
| <Annotation Term="OData.Description" String="This property contains the power sensors."/> |
| <Annotation Term="OData.LongDescription" String="This type shall contain properties that describe power sensor readings for a circuit."/> |
| <NavigationProperty Name="Line1ToLine2" Type="Sensor.Sensor"> |
| <Annotation Term="OData.Permissions" EnumMember="OData.Permission/Read"/> |
| <Annotation Term="Redfish.ExcerptCopy" String="Power"/> |
| <Annotation Term="OData.Description" String="The Line 1 to Line 2 power reading for this circuit."/> |
| <Annotation Term="OData.LongDescription" String="This property shall contain a PowerSensor excerpt that measures power between L1 and L2. This property shall not be present if the circuit does not include an L1-L2 measurement."/> |
| </NavigationProperty> |
| <NavigationProperty Name="Line2ToLine3" Type="Sensor.Sensor"> |
| <Annotation Term="OData.Permissions" EnumMember="OData.Permission/Read"/> |
| <Annotation Term="Redfish.ExcerptCopy" String="Power"/> |
| <Annotation Term="OData.Description" String="The Line 2 to Line 3 power reading for this circuit."/> |
| <Annotation Term="OData.LongDescription" String="This property shall contain a PowerSensor excerpt that measures power between L2 and L3. This property shall not be present if the circuit does not include an L2-L3 measurement."/> |
| </NavigationProperty> |
| <NavigationProperty Name="Line3ToLine1" Type="Sensor.Sensor"> |
| <Annotation Term="OData.Permissions" EnumMember="OData.Permission/Read"/> |
| <Annotation Term="Redfish.ExcerptCopy" String="Power"/> |
| <Annotation Term="OData.Description" String="The Line 3 to Line 1 power reading for this circuit."/> |
| <Annotation Term="OData.LongDescription" String="This property shall contain a PowerSensor excerpt that measures power between L3 and L1. This property shall not be present if the circuit does not include an L3-L1 measurement."/> |
| </NavigationProperty> |
| <NavigationProperty Name="Line1ToNeutral" Type="Sensor.Sensor"> |
| <Annotation Term="OData.Permissions" EnumMember="OData.Permission/Read"/> |
| <Annotation Term="Redfish.ExcerptCopy" String="Power"/> |
| <Annotation Term="OData.Description" String="The Line 1 to Neutral power reading for this circuit."/> |
| <Annotation Term="OData.LongDescription" String="This property shall contain a PowerSensor excerpt that measures power between L1 and Neutral. This property shall not be present if the circuit does not include an L1-Neutral measurement."/> |
| </NavigationProperty> |
| <NavigationProperty Name="Line2ToNeutral" Type="Sensor.Sensor"> |
| <Annotation Term="OData.Permissions" EnumMember="OData.Permission/Read"/> |
| <Annotation Term="Redfish.ExcerptCopy" String="Power"/> |
| <Annotation Term="OData.Description" String="The Line 2 to Neutral power reading for this circuit."/> |
| <Annotation Term="OData.LongDescription" String="This property shall contain a PowerSensor excerpt that measures power between L2 and Neutral. This property shall not be present if the circuit does not include an L2-Neutral measurement."/> |
| </NavigationProperty> |
| <NavigationProperty Name="Line3ToNeutral" Type="Sensor.Sensor"> |
| <Annotation Term="OData.Permissions" EnumMember="OData.Permission/Read"/> |
| <Annotation Term="Redfish.ExcerptCopy" String="Power"/> |
| <Annotation Term="OData.Description" String="The Line 3 to Neutral power reading for this circuit."/> |
| <Annotation Term="OData.LongDescription" String="This property shall contain a PowerSensor excerpt that measures power between L3 and Neutral. This property shall not be present if the circuit does not include an L3-Neutral measurement."/> |
| </NavigationProperty> |
| </ComplexType> |
| |
| <EnumType Name="CircuitType"> |
| <Member Name="Mains"> |
| <Annotation Term="OData.Description" String="A mains input or utility circuit."/> |
| </Member> |
| <Member Name="Branch"> |
| <Annotation Term="OData.Description" String="A branch (output) circuit."/> |
| </Member> |
| <Member Name="Subfeed"> |
| <Annotation Term="OData.Description" String="A subfeed (output) circuit."/> |
| </Member> |
| <Member Name="Feeder"> |
| <Annotation Term="OData.Description" String="A feeder (output) circuit."/> |
| </Member> |
| </EnumType> |
| |
| <EnumType Name="VoltageType"> |
| <Member Name="AC"> |
| <Annotation Term="OData.Description" String="Alternating Current (AC) circuit."/> |
| </Member> |
| <Member Name="DC"> |
| <Annotation Term="OData.Description" String="Direct Current (DC) circuit."/> |
| </Member> |
| </EnumType> |
| </Schema> |
| |
| <Schema xmlns="http://docs.oasis-open.org/odata/ns/edm" Namespace="Circuit.v1_0_1"> |
| <Annotation Term="Redfish.OwningEntity" String="DMTF"/> |
| <Annotation Term="OData.Description" String="This version was created to correct various typographical errors."/> |
| <EntityType Name="Circuit" BaseType="Circuit.v1_0_0.Circuit"/> |
| </Schema> |
| |
| </edmx:DataServices> |
| </edmx:Edmx> |