| *** Settings *** |
| Documentation Getting the systems power sensor readings for voltages. |
| |
| Resource ../../lib/bmc_redfish_resource.robot |
| Resource ../../lib/bmc_redfish_utils.robot |
| Resource ../../lib/openbmc_ffdc.robot |
| Library ../../lib/gen_robot_valid.py |
| |
| Suite Setup Suite Setup Execution |
| Suite Teardown Suite Teardown Execution |
| Test Setup Printn |
| Test Teardown Test Teardown Execution |
| |
| |
| *** Test Cases *** |
| |
| Get Power Sensor Voltage Records |
| [Documentation] Get the power voltage records. |
| [Tags] Get_Power_Sensor_Voltage_Records |
| [Template] Get Voltage Records and Verify |
| |
| # record_type reading_type |
| Voltages ReadingVolts |
| |
| |
| *** Keywords *** |
| |
| Get Voltage Records and Verify |
| [Documentation] Get the power records for voltages. |
| [Arguments] ${record_type} ${reading_type} |
| |
| # Description of Arguments(s): |
| # record_type The sensor record type (e.g. "Voltages") |
| # reading_type The power voltage readings (e.g. "ReadingVolts") |
| |
| # A valid record will have "State" key "Enabled" and "Health" key "OK" |
| ${records}= Redfish.Get Attribute |
| ... ${REDFISH_CHASSIS_POWER_URI} ${record_type} |
| |
| ${num_records}= Get Length ${records} |
| Rprint Vars num_records records fmt=terse |
| |
| ${invalid_records}= Filter Struct ${records} |
| ... [('Health', '^OK$'), ('State', '^Enabled$'), ('${reading_type}', '')] regex=1 invert=1 |
| ${num_invalid_records}= Get Length ${invalid_records} |
| |
| Run Keyword If ${num_invalid_records} > ${0} |
| ... Rprint Vars num_invalid_records invalid_records fmt=terse |
| Valid Value num_invalid_records valid_values=[0] |
| |
| ${cmd} Catenate [x for x in ${records} |
| ... if not x['LowerThresholdNonCritical'] <= x['ReadingVolts'] <= x['UpperThresholdNonCritical']] |
| ${invalid_records}= Evaluate ${cmd} |
| |
| ${num_invalid_records}= Get Length ${invalid_records} |
| Run Keyword If ${num_invalid_records} > ${0} |
| ... Rprint Vars num_invalid_records invalid_records fmt=terse |
| Valid Value num_invalid_records valid_values=[0] |
| |
| |
| Suite Teardown Execution |
| [Documentation] Do the post suite teardown. |
| |
| Redfish.Logout |
| |
| |
| Suite Setup Execution |
| [Documentation] Do test case setup tasks. |
| |
| Printn |
| Redfish Power On stack_mode=skip |
| Redfish.Login |
| |
| |
| Test Teardown Execution |
| [Documentation] Do the post test teardown. |
| |
| FFDC On Test Case Fail |