Joy Onyerikwu | 26975f0 | 2018-05-08 12:55:12 -0500 | [diff] [blame] | 1 | *** Settings *** |
| 2 | |
| 3 | Documentation Verify that both the air and water cooled systems are |
| 4 | ... operating in the allowable ranges for fans, power and temperature |
| 5 | ... during idle and stress up at the OS. |
| 6 | |
| 7 | |
| 8 | # TEST PARAMETERS: |
| 9 | # OPENBMC_HOST The BMC host name or IP address. |
| 10 | # OPENBMC_USERNAME The BMC user name. |
| 11 | # OPENBMC_PASSWORD The BMC password. |
| 12 | # OS_HOST The OS host name or IP address. |
| 13 | # OS_USERNAME The OS user name. |
| 14 | # OS_PASSWORD The OS Host password. |
| 15 | # HTX_DURATION Duration of the HTX run (e.g 1h, 20m). |
| 16 | # HTX_INTERVAL The time delay between consecutive |
| 17 | # checks for temperature, fan and power |
| 18 | # ranges. |
| 19 | # HTX_MDT_PROFILE The MDT Profile to run. |
| 20 | # |
| 21 | # The parameters below should be comma-separated lists, |
| 22 | # (e.g "500,800"). See default ranges below. |
| 23 | # These ranges can vary based on the type of system under test. |
| 24 | # |
| 25 | # FAN_SPEED_RANGE_IDLE The allowable range of fan speeds, |
| 26 | # expressed as RPMs, when the machine is |
| 27 | # at an idle state. |
| 28 | # FAN_SPEED_RANGE_STRESS The allowable range of fan speeds, |
| 29 | # expressed as RPMs, when the machine is |
| 30 | # at a stressed state. |
| 31 | # TEMPERATURE_RANGE_IDLE The allowed range for temperature, |
| 32 | # expressed as Celsius degrees, when |
| 33 | # the machine is at an idle state. |
| 34 | # TEMPERATURE_RANGE_STRESS The allowable range for temperature, |
| 35 | # expressed as Celsius degrees, when |
| 36 | # the machine is at a stressed state. |
| 37 | # POWER_RANGE_IDLE The allowable range for power, expressed |
| 38 | # in Watts, while the machine is at an |
| 39 | # idle state. |
| 40 | # POWER_RANGE_STRESS The allowable range for power, expressed |
| 41 | # in Watts, while the machine is at a |
| 42 | # stressed state. |
| 43 | |
| 44 | |
| 45 | Resource ../syslib/utils_os.robot |
| 46 | Resource ../lib/fan_utils.robot |
| 47 | Library ../lib/gen_robot_valid.py |
| 48 | Suite Setup Suite Setup Execution |
| 49 | Test Teardown FFDC On Test Case Fail |
| 50 | Suite Teardown Shutdown HTX Exerciser |
| 51 | |
| 52 | *** Variables *** |
| 53 | # Default Ranges. |
| 54 | @{FAN_SPEED_RANGE_IDLE}= 0 6000 |
| 55 | @{FAN_SPEED_RANGE_STRESS}= 3000 8000 |
| 56 | @{TEMPERATURE_RANGE_IDLE}= 30 45 |
| 57 | @{TEMPERATURE_RANGE_STRESS}= 35 100 |
| 58 | @{POWER_RANGE_IDLE}= 15 60 |
| 59 | @{POWER_RANGE_STRESS}= 30 350 |
| 60 | |
| 61 | |
| 62 | *** Test Cases *** |
| 63 | |
| 64 | Verify Fan Speeds During Idle State |
| 65 | [Documentation] Verify the fan speeds are within acceptable range |
| 66 | ... while the system is idle. |
| 67 | [Tags] Verify_Fan_Speeds_During_Idle_State |
| 68 | |
| 69 | Verify Fan Speeds ${FAN_SPEED_RANGE_IDLE} |
| 70 | |
| 71 | |
| 72 | Verify Temperature During Idle State |
| 73 | [Documentation] Verify the temperature values are within acceptable |
| 74 | ... range while the system is idle. |
| 75 | [Tags] Verify_Temperature_During_Idle_State |
| 76 | |
| 77 | Verify Temperatures ${TEMPERATURE_RANGE_IDLE} |
| 78 | |
| 79 | |
| 80 | Verify Power During Idle State |
| 81 | [Documentation] Verify the power values are within acceptable range |
| 82 | ... while the system is idle. |
| 83 | [Tags] Verify_Power_During_Idle_State |
| 84 | |
| 85 | Verify Power Values ${POWER_RANGE_IDLE} |
| 86 | |
| 87 | |
| 88 | Test Hardware Limits During Stress |
| 89 | [Documentation] Verify the hardware under stress is within |
| 90 | ... acceptable range. |
| 91 | [Tags] Test_Hardware_Limits_During_Stress |
| 92 | |
| 93 | # Run HTX and verify, within intervals, that the hardware ranges |
| 94 | # are within the allowable ranges. |
| 95 | Run MDT Profile |
| 96 | Repeat Keyword ${HTX_DURATION} Run Keywords |
| 97 | ... Verify Fan Speeds ${FAN_SPEED_RANGE_STRESS} |
| 98 | ... AND Verify Temperatures ${TEMPERATURE_RANGE_STRESS} |
| 99 | ... AND Verify Power Values ${POWER_RANGE_STRESS} |
| 100 | ... AND Run Key Sleep \ ${HTX_INTERVAL} |
| 101 | |
| 102 | |
| 103 | *** Keywords *** |
| 104 | |
| 105 | Verify Fan Speeds |
| 106 | [Documentation] Verify that the fan speeds are within the required |
| 107 | ... range. |
| 108 | [Arguments] ${range} |
| 109 | |
| 110 | # Description of argument(s): |
| 111 | # range A 2-element list comprised of the lower |
| 112 | # and upper values which constitute the |
| 113 | # valid range for the fan speeds. |
| 114 | # (e.g [500,800]). |
| 115 | |
| 116 | # Get the fans with the lowest and highest fan speeds. Verify that |
| 117 | # the speeds are within the proper range. |
| 118 | ${fan_objects}= Read Properties ${SENSORS_URI}fan_tach/enumerate |
| 119 | ${fan_speeds}= Evaluate |
| 120 | ... [ x['Value'] for x in $fan_objects.values() ] |
| 121 | ${max_fan_speed} Evaluate max(map(int, $fan_speeds)) |
| 122 | ${min_fan_speed} Evaluate min(map(int, $fan_speeds)) |
| 123 | Rvalid Range max_fan_speed ${range} |
| 124 | Rvalid Range min_fan_speed ${range} |
| 125 | |
| 126 | |
| 127 | Verify Temperatures |
| 128 | [Documentation] Verify that the temperature values are within the |
| 129 | ... required range. |
| 130 | [Arguments] ${range} |
| 131 | |
| 132 | # Description of argument(s): |
| 133 | # range The allowable range for the temperature, |
| 134 | # values (e.g [20,60]). |
| 135 | |
| 136 | # Get the lowest and highest temperatures for GPUs, verify |
| 137 | # that it is within the proper range. |
| 138 | ${gpu_max_temperature}= Get GPU Max Temperature |
| 139 | ${gpu_min_temperature}= Get GPU Min Temperature |
| 140 | Rvalid Range gpu_max_temperature ${range} |
| 141 | Rvalid Range gpu_min_temperature ${range} |
| 142 | # Verify for CPUs. |
| 143 | ${cpu_highest_temp}= Get CPU Max Temperature |
| 144 | ${cpu_lowest_temp}= Get CPU Min Temperature |
| 145 | Rvalid Range cpu_highest_temp ${range} |
| 146 | Rvalid Range cpu_lowest_temp ${range} |
| 147 | |
| 148 | |
| 149 | Verify Power Values |
| 150 | [Documentation] Verify that the power values for GPUs and CPUs |
| 151 | ... are within the required range. |
| 152 | [Arguments] ${range} |
| 153 | |
| 154 | # Description of argument(s): |
| 155 | # range The allowable range for power values, |
| 156 | # (e.g [15,30]). |
| 157 | |
| 158 | ${gpu_max}= Get GPU Max Power |
| 159 | ${gpu_min}= Get GPU Min Power |
| 160 | ${gpu_max_power}= Evaluate int(round(${gpu_max})) |
| 161 | ${gpu_min_power}= Evaluate int(round(${gpu_min})) |
| 162 | Rvalid Range gpu_max_power ${range} |
| 163 | Rvalid Range gpu_min_power ${range} |
| 164 | |
| 165 | ${p0}= Read Properties ${SENSORS_URI}power/p0_power |
| 166 | ${p1}= Read Properties ${SENSORS_URI}power/p1_power |
| 167 | # The scaling factor for fans is -6 for CPU power values. |
| 168 | ${p0_value}= Evaluate ${p0}['Value']/1000000 |
| 169 | ${p1_value}= Evaluate ${p1}['Value']/1000000 |
| 170 | Rvalid Range p0_value ${range} |
| 171 | Rvalid Range p1_value ${range} |
| 172 | |
| 173 | |
| 174 | Suite Setup Execution |
| 175 | [Documentation] Do suite setup tasks. |
| 176 | |
| 177 | REST Power On stack_mode=skip |
| 178 | ${htx_running}= Is HTX Running |
| 179 | Should Not Be True ${htx_running} msg=HTX needs to be shutdown. |