| #include "occ_status.hpp" |
| |
| #include "occ_manager.hpp" |
| #include "occ_sensor.hpp" |
| #include "powermode.hpp" |
| #include "utils.hpp" |
| |
| #include <fmt/core.h> |
| |
| #ifdef POWER10 |
| #include <com/ibm/Host/Target/server.hpp> |
| #endif |
| #include <phosphor-logging/log.hpp> |
| |
| #include <filesystem> |
| |
| namespace open_power |
| { |
| namespace occ |
| { |
| |
| using namespace phosphor::logging; |
| |
| // Handles updates to occActive property |
| bool Status::occActive(bool value) |
| { |
| if (value != this->occActive()) |
| { |
| log<level::INFO>(fmt::format("Status::occActive OCC{} changed to {}", |
| instance, value) |
| .c_str()); |
| if (value) |
| { |
| // Bind the device |
| device.bind(); |
| |
| // Start watching for errors |
| addErrorWatch(); |
| |
| // Reset last OCC state |
| lastState = 0; |
| |
| if (device.master()) |
| { |
| // Update powercap bounds from OCC |
| manager.updatePcapBounds(); |
| } |
| |
| // Update the OCC active sensor before notifying Manager |
| Base::Status::occActive(value); |
| |
| // Call into Manager to let know that we have bound |
| if (this->managerCallBack) |
| { |
| this->managerCallBack(instance, value); |
| } |
| } |
| else |
| { |
| #ifdef POWER10 |
| if (pmode && device.master()) |
| { |
| // Prevent mode changes |
| pmode->setMasterActive(false); |
| } |
| if (safeStateDelayTimer.isEnabled()) |
| { |
| // stop safe delay timer |
| safeStateDelayTimer.setEnabled(false); |
| } |
| #endif |
| // Call into Manager to let know that we will unbind. |
| if (this->managerCallBack) |
| { |
| this->managerCallBack(instance, value); |
| } |
| |
| // Stop watching for errors |
| removeErrorWatch(); |
| |
| // Do the unbind. |
| device.unBind(); |
| } |
| } |
| else if (value && !device.bound()) |
| { |
| // Existing error watch is on a dead file descriptor. |
| removeErrorWatch(); |
| |
| /* |
| * In it's constructor, Status checks Device::bound() to see if OCC is |
| * active or not. |
| * Device::bound() checks for occX-dev0 directory. |
| * We will lose occX-dev0 directories during FSI rescan. |
| * So, if we start this application (and construct Status), and then |
| * later do FSI rescan, we will end up with occActive = true and device |
| * NOT bound. Lets correct that situation here. |
| */ |
| device.bind(); |
| |
| // Add error watch again |
| addErrorWatch(); |
| } |
| else if (!value && device.bound()) |
| { |
| removeErrorWatch(); |
| |
| // In the event that the application never receives the active signal |
| // even though the OCC is active (this can occur if the BMC is rebooted |
| // with the host on, since the initial OCC driver probe will discover |
| // the OCCs), this application needs to be able to unbind the device |
| // when we get the OCC inactive signal. |
| device.unBind(); |
| } |
| return Base::Status::occActive(value); |
| } |
| |
| // Callback handler when a device error is reported. |
| void Status::deviceError() |
| { |
| #ifdef POWER10 |
| if (pmode && device.master()) |
| { |
| // Prevent mode changes |
| pmode->setMasterActive(false); |
| } |
| #endif |
| |
| // This would deem OCC inactive |
| this->occActive(false); |
| |
| // Reset the OCC |
| this->resetOCC(); |
| } |
| |
| // Sends message to host control command handler to reset OCC |
| void Status::resetOCC() |
| { |
| log<level::INFO>( |
| fmt::format(">>Status::resetOCC() - requesting reset for OCC{}", |
| instance) |
| .c_str()); |
| #ifdef PLDM |
| if (resetCallBack) |
| { |
| this->resetCallBack(instance); |
| } |
| #else |
| constexpr auto CONTROL_HOST_PATH = "/org/open_power/control/host0"; |
| constexpr auto CONTROL_HOST_INTF = "org.open_power.Control.Host"; |
| |
| // This will throw exception on failure |
| auto service = utils::getService(CONTROL_HOST_PATH, CONTROL_HOST_INTF); |
| |
| auto& bus = utils::getBus(); |
| auto method = bus.new_method_call(service.c_str(), CONTROL_HOST_PATH, |
| CONTROL_HOST_INTF, "Execute"); |
| // OCC Reset control command |
| method.append(convertForMessage(Control::Host::Command::OCCReset).c_str()); |
| |
| // OCC Sensor ID for callout reasons |
| method.append(std::variant<uint8_t>(std::get<0>(sensorMap.at(instance)))); |
| bus.call_noreply(method); |
| return; |
| #endif |
| } |
| |
| // Handler called by Host control command handler to convey the |
| // status of the executed command |
| void Status::hostControlEvent(sdbusplus::message::message& msg) |
| { |
| std::string cmdCompleted{}; |
| std::string cmdStatus{}; |
| |
| msg.read(cmdCompleted, cmdStatus); |
| |
| log<level::DEBUG>("Host control signal values", |
| entry("COMMAND=%s", cmdCompleted.c_str()), |
| entry("STATUS=%s", cmdStatus.c_str())); |
| |
| if (Control::Host::convertResultFromString(cmdStatus) != |
| Control::Host::Result::Success) |
| { |
| if (Control::Host::convertCommandFromString(cmdCompleted) == |
| Control::Host::Command::OCCReset) |
| { |
| // Must be a Timeout. Log an Error trace |
| log<level::ERR>( |
| "Error resetting the OCC.", entry("PATH=%s", path.c_str()), |
| entry("SENSORID=0x%X", std::get<0>(sensorMap.at(instance)))); |
| } |
| } |
| return; |
| } |
| |
| // Called from Manager::pollerTimerExpired() in preperation to POLL OCC. |
| void Status::readOccState() |
| { |
| currentOccReadRetriesCount = occReadRetries; |
| occReadStateNow(); |
| } |
| |
| #ifdef POWER10 |
| // Special processing that needs to happen once the OCCs change to ACTIVE state |
| void Status::occsWentActive() |
| { |
| CmdStatus status = CmdStatus::SUCCESS; |
| |
| status = pmode->sendModeChange(); |
| if (status != CmdStatus::SUCCESS) |
| { |
| log<level::ERR>( |
| fmt::format( |
| "Status::occsWentActive: OCC mode change failed with status {}", |
| status) |
| .c_str()); |
| |
| // Disable and reset to try recovering |
| deviceError(); |
| } |
| |
| status = pmode->sendIpsData(); |
| if (status != CmdStatus::SUCCESS) |
| { |
| log<level::ERR>( |
| fmt::format( |
| "Status::occsWentActive: Sending Idle Power Save Config data failed with status {}", |
| status) |
| .c_str()); |
| |
| if (status == CmdStatus::COMM_FAILURE) |
| { |
| // Disable and reset to try recovering |
| deviceError(); |
| } |
| } |
| } |
| |
| // Send Ambient and Altitude to the OCC |
| CmdStatus Status::sendAmbient(const uint8_t inTemp, const uint16_t inAltitude) |
| { |
| CmdStatus status = CmdStatus::FAILURE; |
| bool ambientValid = true; |
| uint8_t ambientTemp = inTemp; |
| uint16_t altitude = inAltitude; |
| |
| if (ambientTemp == 0xFF) |
| { |
| // Get latest readings from manager |
| manager.getAmbientData(ambientValid, ambientTemp, altitude); |
| log<level::DEBUG>( |
| fmt::format("sendAmbient: valid: {}, Ambient: {}C, altitude: {}m", |
| ambientValid, ambientTemp, altitude) |
| .c_str()); |
| } |
| |
| std::vector<std::uint8_t> cmd, rsp; |
| cmd.reserve(11); |
| cmd.push_back(uint8_t(CmdType::SEND_AMBIENT)); |
| cmd.push_back(0x00); // Data Length (2 bytes) |
| cmd.push_back(0x08); // |
| cmd.push_back(0x00); // Version |
| cmd.push_back(ambientValid ? 0 : 0xFF); // Ambient Status |
| cmd.push_back(ambientTemp); // Ambient Temperature |
| cmd.push_back(altitude >> 8); // Altitude in meters (2 bytes) |
| cmd.push_back(altitude & 0xFF); // |
| cmd.push_back(0x00); // Reserved (3 bytes) |
| cmd.push_back(0x00); |
| cmd.push_back(0x00); |
| log<level::DEBUG>(fmt::format("sendAmbient: SEND_AMBIENT " |
| "command to OCC{} ({} bytes)", |
| instance, cmd.size()) |
| .c_str()); |
| status = occCmd.send(cmd, rsp); |
| if (status == CmdStatus::SUCCESS) |
| { |
| if (rsp.size() == 5) |
| { |
| if (RspStatus::SUCCESS != RspStatus(rsp[2])) |
| { |
| log<level::ERR>( |
| fmt::format( |
| "sendAmbient: SEND_AMBIENT failed with rspStatus 0x{:02X}", |
| rsp[2]) |
| .c_str()); |
| dump_hex(rsp); |
| status = CmdStatus::FAILURE; |
| } |
| } |
| else |
| { |
| log<level::ERR>( |
| fmt::format( |
| "sendAmbient: INVALID SEND_AMBIENT response length:{}", |
| rsp.size()) |
| .c_str()); |
| dump_hex(rsp); |
| status = CmdStatus::FAILURE; |
| } |
| } |
| else |
| { |
| log<level::ERR>( |
| fmt::format( |
| "sendAmbient: SEND_AMBIENT FAILED! with status 0x{:02X}", |
| status) |
| .c_str()); |
| |
| if (status == CmdStatus::COMM_FAILURE) |
| { |
| // Disable and reset to try recovering |
| deviceError(); |
| } |
| } |
| |
| return status; |
| } |
| |
| // Called when safe timer expires to determine if OCCs need to be reset |
| void Status::safeStateDelayExpired() |
| { |
| if (this->occActive()) |
| { |
| log<level::INFO>( |
| fmt::format( |
| "safeStateDelayExpired: OCC{} is in SAFE state, requesting reset", |
| instance) |
| .c_str()); |
| // Disable and reset to try recovering |
| deviceError(); |
| } |
| } |
| #endif // POWER10 |
| |
| fs::path Status::getHwmonPath() |
| { |
| using namespace std::literals::string_literals; |
| |
| if (!fs::exists(hwmonPath)) |
| { |
| static bool tracedFail[8] = {0}; |
| |
| if (!hwmonPath.empty()) |
| { |
| log<level::ERR>( |
| fmt::format("Status::getHwmonPath(): path no longer exists: {}", |
| hwmonPath.c_str()) |
| .c_str()); |
| hwmonPath.clear(); |
| } |
| |
| // Build the base HWMON path |
| fs::path prefixPath = |
| fs::path{OCC_HWMON_PATH + "occ-hwmon."s + |
| std::to_string(instance + 1) + "/hwmon/"s}; |
| |
| // Get the hwmonXX directory name |
| try |
| { |
| // there should only be one directory |
| const int numDirs = std::distance( |
| fs::directory_iterator(prefixPath), fs::directory_iterator{}); |
| if (numDirs == 1) |
| { |
| hwmonPath = *fs::directory_iterator(prefixPath); |
| tracedFail[instance] = false; |
| } |
| else |
| { |
| if (!tracedFail[instance]) |
| { |
| log<level::ERR>( |
| fmt::format( |
| "Status::getHwmonPath(): Found multiple ({}) hwmon paths!", |
| numDirs) |
| .c_str()); |
| tracedFail[instance] = true; |
| } |
| } |
| } |
| catch (const fs::filesystem_error& e) |
| { |
| if (!tracedFail[instance]) |
| { |
| log<level::ERR>( |
| fmt::format( |
| "Status::getHwmonPath(): error accessing {}: {}", |
| prefixPath.c_str(), e.what()) |
| .c_str()); |
| tracedFail[instance] = true; |
| } |
| } |
| } |
| |
| return hwmonPath; |
| } |
| |
| // Called to read state and upon failure to read after occReadStateFailTimer. |
| void Status::occReadStateNow() |
| { |
| unsigned int state; |
| const fs::path filename = |
| fs::path(DEV_PATH) / |
| fs::path(sysfsName + "." + std::to_string(instance + 1)) / "occ_state"; |
| |
| std::ifstream file; |
| bool goodFile = false; |
| |
| // open file. |
| file.open(filename, std::ios::in); |
| const int openErrno = errno; |
| |
| // File is open and state can be used. |
| if (file.is_open() && file.good()) |
| { |
| goodFile = true; |
| file >> state; |
| |
| if (state != lastState) |
| { |
| // Trace OCC state changes |
| log<level::INFO>( |
| fmt::format("Status::readOccState: OCC{} state 0x{:02X}", |
| instance, state) |
| .c_str()); |
| lastState = state; |
| #ifdef POWER10 |
| if (OccState(state) == OccState::ACTIVE) |
| { |
| if (pmode && device.master()) |
| { |
| // Set the master OCC on the PowerMode object |
| pmode->setMasterOcc(path); |
| // Enable mode changes |
| pmode->setMasterActive(); |
| |
| // Special processing by master OCC when it goes active |
| occsWentActive(); |
| } |
| |
| CmdStatus status = sendAmbient(); |
| if (status != CmdStatus::SUCCESS) |
| { |
| log<level::ERR>( |
| fmt::format( |
| "readOccState: Sending Ambient failed with status {}", |
| status) |
| .c_str()); |
| } |
| } |
| |
| // If OCC in known Good State. |
| if ((OccState(state) == OccState::ACTIVE) || |
| (OccState(state) == OccState::CHARACTERIZATION) || |
| (OccState(state) == OccState::OBSERVATION)) |
| { |
| // Good OCC State then sensors valid again |
| stateValid = true; |
| |
| if (safeStateDelayTimer.isEnabled()) |
| { |
| // stop safe delay timer (no longer in SAFE state) |
| safeStateDelayTimer.setEnabled(false); |
| } |
| } |
| // Else not Valid state We would be in SAFE mode. |
| // This captures both SAFE mode, and 0x00, or other invalid |
| // state values. |
| else |
| { |
| if (!safeStateDelayTimer.isEnabled()) |
| { |
| // start safe delay timer (before requesting reset) |
| using namespace std::literals::chrono_literals; |
| safeStateDelayTimer.restartOnce(60s); |
| } |
| // Not valid state, update sensors to Nan & not functional. |
| stateValid = false; |
| } |
| #else |
| // Before P10 state not checked, only used good file open. |
| stateValid = true; |
| #endif |
| } |
| } |
| file.close(); |
| |
| // if failed to Read a state or not a valid state -> Attempt retry |
| // after 1 Second delay if allowed. |
| if ((!goodFile) || (!stateValid)) |
| { |
| if (!goodFile) |
| { |
| // If not able to read, OCC may be offline |
| log<level::ERR>( |
| fmt::format("Status::readOccState: open failed (errno={})", |
| openErrno) |
| .c_str()); |
| } |
| else |
| { |
| // else this failed due to state not valid. |
| log<level::ERR>( |
| fmt::format( |
| "Status::readOccState: OCC{} Invalid state 0x{:02X}", |
| instance, state) |
| .c_str()); |
| } |
| |
| #ifdef READ_OCC_SENSORS |
| manager.setSensorValueToNonFunctional(instance); |
| #endif |
| |
| // See occReadRetries for number of retry attempts. |
| if (currentOccReadRetriesCount > 0) |
| { |
| --currentOccReadRetriesCount; |
| #ifdef POWER10 |
| using namespace std::chrono_literals; |
| occReadStateFailTimer.restartOnce(1s); |
| #endif |
| } |
| else |
| { |
| #ifdef POWER10 |
| if (!stateValid && occActive()) |
| { |
| if (!safeStateDelayTimer.isEnabled()) |
| { |
| log<level::ERR>( |
| "Starting 60 sec delay timer before requesting a reset"); |
| // start safe delay timer (before requesting reset) |
| using namespace std::literals::chrono_literals; |
| safeStateDelayTimer.restartOnce(60s); |
| } |
| } |
| #else |
| // State could not be determined, set it to NO State. |
| lastState = 0; |
| |
| // Disable the ability to send Failed actions until OCC is |
| // Active again. |
| stateValid = false; |
| |
| // Disable and reset to try recovering |
| deviceError(); |
| #endif |
| } |
| } |
| } |
| |
| } // namespace occ |