| #Example fan zone definitions for phosphor-fan-control |
| |
| #List the properties of the fan zones that are possible in the system. |
| #The zones may be conditional based on certain conditions, such as |
| #different chassis types or water cooled models. The fans themselves |
| #are not listed in this file. They are in a separate YAML file so it |
| #can be machine generated (i.e. from the MRW) if desired. |
| |
| #The general structure is a list of groups of zones, where a group |
| #contains both the zones and the conditions required for the zones |
| #to be valid |
| |
| #The cooling_profile is used along with the zone number to know |
| #which fans in the fan yaml belong in this zone instance. For |
| #example, a fan may only be in zone 0 if it's the air cooled version |
| #of the system, but not with the water cooled version. In that |
| #case, the fan yaml would have a cooling_profile of 'air' to match |
| #the zone cooling profile. |
| |
| #manager_configuration: |
| # power_on_delay: [Number of seconds that phosphor-fan-control --init |
| # should delay after setting fans to full speed on |
| # a power on.] |
| # |
| #zone_configuration: |
| # - zone_conditions: |
| # - name: [Name of a condition, if any.] |
| # |
| # zones: |
| # - zone: [zone number] |
| # cooling_profiles: |
| # - [cooling profile] |
| # full_speed: [Full speed for the zone.] |
| # default_floor: [Default floor speed for the zone that fan speeds can |
| # not go below.] |
| # increase_delay: [Number of seconds to delay additional speed increases |
| # that are less than the speed increase that's currently |
| # occurring.] |
| # decrease_interval: [A repeating number of seconds interval that |
| # requested speed decreases may occur when no speed |
| # increase is occurring at that time as well.] |
| |
| #Example: |
| #manager_configuration: |
| # power_on_delay: 20 |
| # |
| #zone_configuration: |
| # - zone_conditions: |
| # - name: air_cooled_chassis |
| # |
| # zones: |
| # - zone: 0 |
| # cooling_profiles: |
| # - air |
| # - all |
| # full_speed: 10500 |
| # default_floor: 6000 |
| # increase_delay: 5 |
| # decrease_interval: 30 |
| # |
| # - zone_conditions: |
| # - name: water_and_air_cooled_chassis |
| # |
| # zones: |
| # - zone: 0 |
| # cooling_profiles: |
| # - water |
| # - all |
| # full_speed: 4000 |
| # default_floor: 2500 |
| # increase_delay: 5 |
| # decrease_interval: 20 |