| #include "fancontroller.hpp" |
| |
| #include "util.hpp" |
| #include "zone.hpp" |
| |
| #include <algorithm> |
| #include <iostream> |
| |
| std::unique_ptr<PIDController> |
| FanController::CreateFanPid(ZoneInterface* owner, const std::string& id, |
| std::vector<std::string>& inputs, |
| ec::pidinfo initial) |
| { |
| if (inputs.size() == 0) |
| { |
| return nullptr; |
| } |
| auto fan = std::make_unique<FanController>(id, inputs, owner); |
| ec::pid_info_t* info = fan->get_pid_info(); |
| |
| InitializePIDStruct(info, &initial); |
| |
| return fan; |
| } |
| |
| float FanController::input_proc(void) |
| { |
| float sum = 0; |
| double value = 0; |
| std::vector<int64_t> values; |
| std::vector<int64_t>::iterator result; |
| |
| try |
| { |
| for (const auto& name : _inputs) |
| { |
| value = _owner->getCachedValue(name); |
| /* If we have a fan we can't read, its value will be 0 for at least |
| * some boards, while others... the fan will drop off dbus (if |
| * that's how it's being read and in that case its value will never |
| * be updated anymore, which is relatively harmless, except, when |
| * something tries to read its value through IPMI, and can't, they |
| * sort of have to guess -- all the other fans are reporting, why |
| * not this one? Maybe it's unable to be read, so it's "bad." |
| */ |
| if (value > 0) |
| { |
| values.push_back(value); |
| sum += value; |
| } |
| } |
| } |
| catch (const std::exception& e) |
| { |
| std::cerr << "exception on input_proc.\n"; |
| throw; |
| } |
| |
| /* Reset the value from the above loop. */ |
| value = 0; |
| if (values.size() > 0) |
| { |
| /* When this is a configuration option in a later update, this code |
| * will be updated. |
| */ |
| // value = sum / _inputs.size(); |
| |
| /* the fan PID algorithm was unstable with average, and seemed to work |
| * better with minimum. I had considered making this choice a variable |
| * in the configuration, and I will. |
| */ |
| result = std::min_element(values.begin(), values.end()); |
| value = *result; |
| } |
| |
| return static_cast<float>(value); |
| } |
| |
| float FanController::setpt_proc(void) |
| { |
| float maxRPM = _owner->getMaxRPMRequest(); |
| |
| // store for reference, and check if more or less. |
| float prev = get_setpoint(); |
| |
| if (maxRPM > prev) |
| { |
| setFanDirection(FanSpeedDirection::UP); |
| } |
| else if (prev > maxRPM) |
| { |
| setFanDirection(FanSpeedDirection::DOWN); |
| } |
| else |
| { |
| setFanDirection(FanSpeedDirection::NEUTRAL); |
| } |
| |
| set_setpoint(maxRPM); |
| |
| return (maxRPM); |
| } |
| |
| void FanController::output_proc(float value) |
| { |
| float percent = value; |
| |
| /* If doing tuning logging, don't go into failsafe mode. */ |
| #ifndef __TUNING_LOGGING__ |
| if (_owner->getFailSafeMode()) |
| { |
| /* In case it's being set to 100% */ |
| if (percent < _owner->getFailSafePercent()) |
| { |
| percent = _owner->getFailSafePercent(); |
| } |
| } |
| #endif |
| |
| // value and kFanFailSafeDutyCycle are 10 for 10% so let's fix that. |
| percent /= 100; |
| |
| // PidSensorMap for writing. |
| for (auto& it : _inputs) |
| { |
| auto sensor = _owner->getSensor(it); |
| sensor->write(static_cast<double>(percent)); |
| } |
| |
| return; |
| } |